Home/StarBiogas Smart Control/Process Control StarBiogas Smart Control System / production

Process Control

Desulfurization, CO₂ removal, compression, and purification sections are centrally presented in one SCADA view. Temperature, pressure, flow, and level refresh in real-time; trends and alarms are retained together — supporting long-term stable operation.

Process Control Center · PROCESS CONTROL CENTERUtilities · MDEA · TSA · compressor5 SCADA viewsPC and mobile dual-platformPlant running
Process chainBiogas inlet → biomethane grid injection
V1101

Biogas buffer and cooling/drying

Buffer tank stabilizes pressure; chiller removes free water

C-01

Biogas compression

Boost to the pressure required by downstream process steps

T3101

Pretreatment tower

Removes particulates and impurities

T3103

MDEA absorber

Amine solution absorbs CO₂; purified gas exits from tower top

T3104

Solution regeneration tower

Heated desorption of acid gas; lean amine recirculated

F4101

TSA adsorption tower

Three towers switch — temperature-swing adsorption drying/fine removal

AT4101

Grouped online monitoring

CH₄ / CO₂ / O₂ / H₂S and calorific value

C5101

CNG four-stage compression

four-stage compression with inter-stage cooling and separation

Sampling and monitoring pointsT3101→T3103→T3104→F4101→AT4101→ Outlet
Real-time readingsSection values at screenshot time
Biogas compressor discharge pressureReal-time
0.641MPa
PT · compressor
Host currentReal-time
198.00A
I · compressor
Unit load positionReal-time
98.00%
LOAD
Host frequencyReal-time
44.00Hz
HZ · VFD
Oil supply temperatureReal-time
55.00℃
TT · Oil circuit
Exhaust temperatureReal-time
75.30℃
TT · compressor
MDEA biogas inlet flowReal-time
726.18Nm³/h
FT2101
Cumulative 1,222,794 Nm³
Purified gas pressureReal-time
0.61MPa
PT3101
Regeneration tower temperatureReal-time
100.43℃
TT3104
Tower bottom TT3108 120.88 ℃
Acid gas flowReal-time
268.71Nm³/h
FT3102
Cumulative 393,671 Nm³
TSA gas throughputReal-time
203.48Nm³/h
FT4101
Cumulative 404,951 Nm³
TSA adsorption pressureReal-time
0.58MPa
PT4101A
Tower B 0.59 MPa
Regeneration gas temperatureReal-time
97.29℃
TT4107
interlock < 110 ℃
Chiller outlet dew pointReal-time
26.80℃
TT · chiller
Material outlet 11.59 ℃
Design operating condition parametersTBD
TBD
SPEC
Each section range and alarm limit
Post-purification methane concentrationTBD
Pending confirmation
AT4101
Online monitoring items available
Data Sources Groupcentral control systemSCADA viewTag numbers consistent with on-site P&IDsTSA timing sequence T1 420min / T2 200min / T3 360minLimit-crossing triggers alarms and safety interlocks
Sections, tag numbers, and values are all from the group central control system SCADA views (Utilities / MDEA Skid / TSA Skid / Biogas Compressor / CNG Compressor). Above are real-time readings at one moment — not design conditions. Section ranges and alarm limits require business input for replacement.
Core Capabilities

What Process Control does

01

Process Overview

SCADA views drawn from actual P&IDs — equipment status and real-time parameters at a glance.

02

Parameter adjustment

Valve position, frequency, and setpoints remotely commanded within authorized ranges — all actions logged.

03

Alarms & interlocks

Limit-crossing triggers audible-visual alarms and safety interlocks — alarm logs are queryable, actionable, and archivable.

04

Multi-section coverage

Utilities, MDEA Skid, TSA Skid, Biogas Compressor, and CNG Compressor A/B are all included.

mobile

Stay in control of the plant even away from the control room

The same SCADA views adapt to mobile — duty and management staff can access section status, view alarms, and handle events anytime.

Utilities
Utilities
TSA Skid
TSA Skid
Biogas Compressor
Biogas Compressor
About Alarms

Alarm monitoring and logs in this system target process parameter limit-crossings and equipment faults — production control scope, independent from the Video Surveillance system.

Process chain

From biogas inlet to grid injection — eight process sections

Each section has a corresponding SCADA view and real-time monitoring points — tag numbers map one-to-one with field equipment.

V1101

Biogas buffer and cooling/drying

Inlet biogas stabilized by buffer tank; chiller removes free water

C-01

Biogas compression

Boost to the pressure required by downstream processes, with oil temperature and heat dissipation interlocks

T3101

Pretreatment tower

Removes particulates and impurities, protecting downstream packing and membrane modules

T3103

MDEA absorber

Amine solution absorbs CO₂; purified gas exits from tower top

T3104

Solution regeneration tower

Heated desorption of acid gas; lean amine cooled and returned to absorber

F4101

TSA adsorption tower

Three towers switch — temperature-swing adsorption completes drying and fine removal

AT4101

Grouped online monitoring

CH₄ / CO₂ / O₂ / H₂S and calorific value continuous detection

C5101

CNG four-stage compression

Four-stage compression with inter-stage cooling and separation — for loading or grid injection

Tag numbers from on-site SCADA views — consistent with actual P&IDs.
The above sections and tag numbers are from the group central control system SCADA views (Utilities / MDEA Skid / TSA Skid / CNG Compressor) — not schematic.
Real-time monitoring

What each section monitors

Below are monitoring items actually present in SCADA views — continuously acquired by the control system and used in alarm judgment.

01

Biogas Compressorgroup

Full monitoring of intake, exhaust, oil circuit, and motor status — abnormalities can trigger interlock shutdown.

  • Discharge pressure · Suction pressure · Differential pressure
  • Oil supply pressure · Oil supply temperature · Oil separator temperature
  • Phase A/B/C winding temperature · Shaft-end temperature
  • Host current · Host frequency · Unit load position
  • Inlet level · Outlet level · Tank temperature
02

MDEA CO₂ removal skid

Lean/rich amine circulation and regeneration system: temperature, level, flow closed loop.

  • Biogas flow and cumulative total · Purified gas pressure
  • Absorber / regeneration tower level and temperature
  • Lean/rich amine heat exchanger inlet/outlet temperature
  • Acid gas flow and acid gas separator level
  • Amine solution control valve · Purified gas control valve position
03

TSA drying/fine removal skid

Three towers switch by timing sequence — adsorption-regeneration-cooling cycles.

  • T1 / T2 / T3 three-stage timing setup
  • Current step and running time in current step
  • Adsorption tower inlet/outlet pressure and temperature
  • Regeneration gas heating and cooling temperature
  • Temperature alarm/interlock setpoints (tunable)
04

CNG Compressor A/B

Four-stage compression with four-stage cooling and separation, including sound-enclosure environmental monitoring.

  • Discharge pressure and temperature per stage
  • Cooling water pressure · Oil supply pressure and temperature
  • VFD adjustment and feedback · Operating current
  • Tanker docking signal · On-site start/stop and emergency stop
  • Sound enclosure temperature · Ventilation fan and space heater
05

Utilities

Centralized utilities management for steam, demineralized water, nitrogen, cooling water, and wastewater.

  • Steam desuperheating/depressurization and condensate recovery
  • Demineralized water and low-pressure nitrogen supply
  • Cooling water pump and cooling tower fan
  • Wastewater collection tank level and pump
  • Solution storage tank level and lean amine pump
06

Alarms & interlocks

Limit-crossing triggers audible-visual alarms; severe conditions directly trigger interlock protection.

  • Upper/lower alarms, tunable thresholds
  • Alarms pushed to mobile in real time
  • Alarm logs archived — supports handling and root-cause
  • Multi-layer interlock: oil temperature / heat dissipation / ambient temperature
  • Alarm handling records exportable
Real-time readings

A set of actual values from the SCADA view

Below are real-time readings at screenshot time — illustrating monitoring granularity, not representing design conditions.

Biogas compressor discharge pressurePT · compressor
0.641MPa
Oil per-temperature 73.6 ℃ synchronized monitoring
Host currentI · compressor
198.00A
Rated range determined by equipment nameplate
Unit load positionLOAD
98.00%
Full-load operation
Host frequencyHZ
44.00Hz
VFDadjust
MDEA biogas inlet flowFT2101
726.18Nm³/h
Cumulative 1,222,794 Nm³
Purified gas pressurePT3101
0.61MPa
tower toppurified gas
Regeneration tower temperatureTT3104
100.43℃
Regeneration tower bottom TT3108 120.88 ℃
Acid gas flowFT3102
268.71Nm³/h
Cumulative 393,671 Nm³
TSA gas throughputFT4101
203.48Nm³/h
Cumulative 404,951 Nm³
TSA adsorption pressurePT4101A
0.58MPa
Tower B 0.59 MPa
Regeneration gas temperatureTT4107
97.29℃
Interlock set < 110 ℃
Chiller outlet dew pointTT · chiller
26.80℃
Material outlet temperature 11.59 ℃
Values are real-time readings at one moment, from the group central control SCADA view.Design operating condition parameters. Section ranges and alarm limits pending business owner input.
Timing sequence control

TSA three towers auto-switch by preset timing sequence

TSA Skid uses three parallel columns operating in adsorption–regeneration–cooling cycles; timing parameters are tunable within authorized ranges.

Timing sequence stagesetpointFunctionRelated interlocks
T1420 minAdsorption stage — purified gas flows upward through the adsorption towerTT4105 < 110 ℃
T2200 minRegeneration stage — regeneration gas heated and reverse-purgedTT4102 > 55 ℃
T3360 minCooling section — regeneration gas cooler brings gas to standbyTT4107 > 45 ℃
Timing setpoints and interlock conditions from the TSA Skid SCADA view — actual field-set values.
UI reference

Actual system UI

Below are original screenshots of the system backend and mobile app — click to enlarge and view.

SCADA · Utilities
Utilities overview: steam, demineralized water, nitrogen, cooling water, and solution tanks
Utilities overview: steam, demineralized water, nitrogen, cooling water, and solution tanks
SCADA · MDEA Skid
MDEA CO₂ removal: absorber, regeneration tower, lean/rich amine heat exchange and acid gas separation
MDEA CO₂ removal: absorber, regeneration tower, lean/rich amine heat exchange and acid gas separation
SCADA · CNG Compressor
Four-stage compression with inter-stage cooling and separation; oil temperature and heat dissipation interlocks
Four-stage compression with inter-stage cooling and separation; oil temperature and heat dissipation interlocks
SCADA · Biogas Compressor + chiller
Analog, digital, and alarm states centrally monitored; supports remote load adjustment
Analog, digital, and alarm states centrally monitored; supports remote load adjustment